Characteristics of the Product
- Acquired KFI certification
- A product that replaces the combination of NIPPLE and REDUCER
- on sprinkler head direct connection
- Welded and threaded types available
Product Advantage
Economics
- educe material costs by replacing TEE and NIPPLE combination
- Shortened work time and reduced labor costs through easy construction
- No pipe cutting, reduced material loss
Stability
- Reduced risk of leakage and rupture by reducing the joint area of TEE, NIPPLE, and REDUCER
STANDARDS
* The above standards are UL standards. Please inquire separately for KFI standards.
Performance Test Results
Test Item |
Test Standard(KFI) |
KFL |
Pressure-Resistance Test |
When applying 1.5 times of the maximum operating pressure, there should be no cracks, permanent deformation or damage. |
2.1MPa |
Body Strength Test |
When applying 5 times pressure of the highest operating pressure (higher than 1.4MPa), there should be no cracks, permanent deformation or damage. |
7MPa |